Test and Tag Brisbane and Logan

Test and tag in Brisbane and Logan costs from $3.50 to $5.50 per item with Faze Electrical & Airconditioning, depending on the number of items, plus a minimum visit charge of $150 ex GST that covers the first 25 items. Testing is carried out to AS/NZS 3760:2022 by licensed electricians under QLD Electrical Contractor Licence 90552, and every visit includes a tagged asset register, a compliance report and a reminder before your next interval is due. We service offices, warehouses, workshops, schools, clinics, hire fleets and construction sites across Brisbane southside, Logan and Ipswich.

Test and tag Brisbane and Logan

Testing and tagging is the routine inspection and electrical testing of portable appliances, extension leads and power boards to make sure they are safe to keep using. Each item is visually inspected for damage, tested with a portable appliance tester for earth continuity, insulation resistance and polarity, then fitted with a durable tag showing who tested it, the date and the next due date. Items that fail are tagged out of service and you get a clear list of what to repair or replace.

In Queensland this is not just good practice. The Electrical Safety Regulation 2013 requires equipment in higher-risk workplaces such as construction, manufacturing, rural industry and commercial cleaning to be tested and tagged at set intervals, and every business has a general duty under the Work Health and Safety Act 2011 to make sure electrical equipment is safe. AS/NZS 3760:2022 is the standard that defines how the tests are done and how often.

Because Faze is a licensed electrical contractor rather than a tag-only operator, we can also repair leads and boards, replace damaged plugs on the spot, test your fixed safety switches and fix any faults we find in the wiring behind the outlets. One visit, one invoice, one report.

What does test and tag cost per item?

Brisbane test and tag pricing in 2026 sits between roughly $3 and $9.50 per item across the market, with minimum visit fees of $100 to $250. Volume matters more than anything else. A 15-item cafe costs more per item than a 400-item warehouse because the travel and set-up time is the same. Our from-prices are below. All prices are ex GST and confirmed on your written quote once we know the item count, the site type and whether RCD testing is included.

Site size From price per item Notes
1 to 50 items From $5.50 Minimum visit charge $150 covers the first 25 items
51 to 200 items From $4.50 Most offices, clinics, schools and small workshops
201 items and over From $3.50 Warehouses, factories, hire fleets, multi-site accounts
Three-phase equipment From $9.50 Welders, compressors, commercial kitchen equipment
Fixed RCD push-button and trip-time test From $15 per RCD Recorded trip times, combined into the same report
Portable RCD test From $9.50 per unit Site boxes, portable power boards with built-in RCD
Emergency and exit light test Quoted per site Six-monthly to AS 2293, bookable on the same visit

Failed items are tagged out at no extra charge. Minor repairs such as replacing a damaged plug top or a cracked power board are quoted on the day so you can approve them immediately. There are no lock-in contracts, but customers who book recurring visits are given the recurring rate from the first visit.

AS/NZS 3760:2022 testing intervals by environment

The 2022 edition of the standard moved the interval table to Table 2.4 and clarified that intervals depend on the environment the equipment lives in, not the type of business. The summary below covers the environments we see most often in Brisbane and Logan workplaces.

Environment Appliances, leads and power boards Fixed RCD push-button test Portable RCD push-button test RCD trip-time test
Construction and demolition sites (AS/NZS 3012) 3 months Monthly by user Daily or before each use 12 months
Factories, workshops, manufacturing, repair and assembly 6 months 6 months Daily or before each use 12 months
Cords subject to flexing or abuse, hostile environments such as commercial kitchens, wet areas and outdoor use 12 months 6 months 3 months 12 months
Office and retail equipment not subject to flexing (fixed computers, printers, fridges) 5 years 6 months 3 months 2 years
Residential-type areas of hotels, motels, boarding houses, halls 2 years 6 months 6 months 2 years
Commercial cleaning equipment 6 months Not applicable Daily or before each use 6 months
Hire equipment Inspect before each hire, test every 3 months Not applicable Before each hire 12 months

New equipment does not need to be tested before first use, but it does need a tag showing the date it entered service so the first interval can be calculated. Double-insulated (Class II) equipment is tested for insulation only; earthed (Class I) equipment gets earth continuity as well.

RCD and safety switch testing on the same visit

Most sites we visit have never had their fixed safety switches trip-time tested, which is a gap in the compliance record. The push-button test only proves the mechanism moves. The trip-time test uses a calibrated instrument to confirm the switch disconnects within 300 milliseconds at its rated leakage current, which is the test the standard actually asks for. We do both, record the results against each circuit and include them in your report. For a switchboard-wide RCD test on a commercial board, see our commercial switchboard and RCD testing Brisbane page, priced from $185 per board. If your board has no RCDs at all, we can install them on the same day; our safety switch installation Brisbane page explains costs.

What happens on a test and tag visit

  1. We walk the site with you and count the items so the quote matches reality.
  2. Each item is visually inspected, tested and tagged. Items that fail are tagged Do Not Use and set aside.
  3. Fixed and portable RCDs are tested and the trip times recorded.
  4. We repair anything simple on the day with your approval.
  5. You receive an itemised asset register, a signed compliance statement and a next-due reminder, by email within 24 hours.

Visits are scheduled around your operating hours, including early morning, evening and weekend slots for retail, hospitality and schools. As a full electrical contractor we can also cover electrical safety audits, emergency lighting tests, thermal imaging of switchboards and general maintenance under one recurring agreement. Our commercial electricians in Brisbane look after sites from Springwood and Underwood through to Yatala and Wacol.

Frequently asked questions

How much does test and tag cost per item in Brisbane?

In 2026, Brisbane test and tag prices typically run from about $3 to $9.50 per item, with most providers charging a minimum visit fee of $100 to $250. Faze test and tag starts from $5.50 per item for small sites and drops to $3.50 per item for larger volumes. Each price is confirmed on your quote once we know the item count and site type.

Is test and tag a legal requirement in Queensland?

Queensland’s Electrical Safety Regulation 2013 requires specified electrical equipment used in higher-risk workplaces such as construction, manufacturing and commercial cleaning to be inspected, tested and tagged at set intervals. In lower-risk workplaces such as offices, testing and tagging to AS/NZS 3760:2022 is the accepted way to meet your general duty to keep equipment safe.

How often does equipment need to be tested and tagged?

It depends on the environment. Construction and demolition equipment is tested every 3 months, factory and workshop equipment every 6 months, office and retail equipment with cords that get moved every 12 months, and fixed office equipment every 5 years. Hire equipment is inspected before each hire and tested every 3 months. The full table is above.

Does test and tag include safety switch (RCD) testing?

Not automatically, but it should be booked together. AS/NZS 3760:2022 sets separate intervals for push-button RCD tests and for trip-time tests with a calibrated tester. We test your fixed and portable RCDs on the same visit, record the trip times, and issue one combined report so your whole site is covered.

Do you provide a compliance report after testing?

Yes. After every visit you receive an itemised asset register listing each item, its location, tag number, test result and next due date, plus a signed compliance statement. We keep a copy and send you a reminder before the next interval is due, so you never have to chase it.

Book test and tag in Brisbane or Logan

Faze Electrical & Airconditioning is based in Woodridge and covers Logan, Brisbane southside, Ipswich and the northern Gold Coast. QLD Electrical Contractor Licence 90552. ARCtick L181564. Electrical work carries a 12 month workmanship warranty and split system installations 5 years.

Call 07 4428 2766 or request a quote online and we will come back to you the same business day.